Electronic VAR control - 200 A 380..480 V AC - IP00 enclosure

Electronic VAR control - 200 A 380..480 V AC - IP00 enclosure

Part Number: EVCP200D5IP00

UPC:

View full details

Product Description

  • Range Of Product: AccuSine
  • Product Or Component Type: electronic VAR controller
  • Product Name: AccuSine PFV+

Contractual warranty

  • Warranty: 18 months

Complementary

  • Electromagnetic Compatibility: conducted EMC, class A EN 61000-6-4
  • Accessibility For Operation: front
  • Function Available: rear plenum with forced ventilation for high heat flow
  • Input Frequency: 50/60 Hz +/- 3 % auto-sensing
  • Reactive Power Rating: 166 kvar 480 V AC 50/60 Hz
  • Enclosure Mounting: wall mounted
  • Nominal Output Current: 200 A
  • Poles Description: 3P
  • Network Rated Voltage: 380-480 V AC
  • Protection Type: without protection
  • Operating Mode: mains current balancing || volt-var support || power factor correction
  • Location Of Connection: bottom
  • Maximum Permissible Voltage: 1.1 x Un
  • Wiring Mode: 3 or 4 wires
  • Mounting Location: indoor

Offer Sustainability

  • China Rohs Regulation: Product out of China RoHS scope. Substance declaration for your information.
  • Rohs Exemption Information: Yes
  • Mercury Free: Yes
  • Toxic Heavy Metal Free: Yes
  • Eu Rohs Directive: Compliant
  • Reach Regulation: Free of Substances of Very High Concern above the threshold
  • California Proposition 65: WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Reach Free Of Svhc: Yes
  • Weee: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

  • Product Certifications: cULus || ABS || CE || DNV-GL || RCM
  • Relative Humidity: 0-95 %
  • Height: 1323 mm
  • Ambient Air Temperature For Storage: -20-60 °C
  • Standards: EN 61000-6-4 || CSA C22.2 No 14 || EN 60439-1 || UL 508 || CSA C22.2 No 60947-1-07 || UL 60947-1
  • Ambient Air Temperature For Operation: 0-40 °C || 0-50 °C maximum with current derating of 2 % per °C
  • Operating Altitude: <= 3280.84 ft (1000 m) 1 % per 100 m
  • Color: Light gray RAL 7035)
  • Width: 582 mm
  • Environmental Characteristic: operating 3C2 IEC 60721-3-3 || operating 3S2 IEC 60721-3-3 || storage 3C3 IEC 60721-3-3 || storage 3S3 IEC 60721-3-3
  • Depth: 438 mm
  • Net Weight: 175 kg
  • Ip Degree Of Protection: IP00
  • Impregnation Material: conformal coated
Spec Sheet

CAD

Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-right (dwg)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-back (dxf)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-front (dxf)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-back (dwg)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140 (pdf)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-top (dxf)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-bottom (dxf)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-left (dxf)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_3D-simplified (stp)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-top (dwg)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-left (dwg)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-bottom (dwg)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-right (dxf)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-isometric (dxf)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-front (dwg)
Active harmonic filter 200 amp Enclosure - 3D CAD - MCADDE0000140_2D-isometric (dwg)

User guide

PowerLogic™ AccuSine Firmware User Manual - PKR30257-00 (pdf)
Installation Manual: AccuSine PCS+™ Active Harmonic Filter / AccuSine PFV+™ Electronic VAR Correction - NHA41798-02 (pdf)
PowerLogic™ AccuSine PCS+, PFV+, and PCSn User Manual - JYT20814EN-00 (pdf)