Skip to product information
1 of 1

Easergy SC150 CT-LPVT/VT: Switch controller - 1/5 A - LPVT/VT sensors

Easergy SC150 CT-LPVT/VT: Switch controller - 1/5 A - LPVT/VT sensors

Part Number: EMS59201

UPC:

View full details

Product Description

  • Range Of Product: Easergy T300
  • Device Short Name: SC150

Complementary

  • Communication Port Support: 2 ETHERNET RJ45
  • Measurement Voltage: LPVT single or three phases)0-10 V AC 50/60 Hz || VTs single or three phases)47-240 V AC 50/60 Hz
  • Number Of Outputs: switch 2 digital (relay)
  • Continuous Output Current: 8 A
  • Memory Capacity: 4 MB
  • Output Voltage: motor 12...127 V DC || motor 90...220 V AC
  • Protection Type: ANSI 50/51 : overcurrent || ANSI 50N/51N : earth fault || ANSI 67 : directional phase overcurrent || ANSI 67N : directional earth fault || ANSI 47 : negative sequence overvoltage || ANSI 27 : undervoltage || ANSI 59 : overvoltage || ANSI 59N : neutral voltage displacement || ANSI 37 : phase undercurrent
  • Type Of Measurement: apparent power || voltage || active and reactive power || active and reactive energy || power factor || current || frequency || apparent energy
  • Product Or Component Type: MV switch controller
  • Irms Rated Making Capacity: 15 A 4 s
  • Measurement Current: 5-5 A || 1-1 A
  • Maximum Switching Voltage: 440 V AC
  • Number Of Inputs: 8 digital IEC 61131-2 type 3
  • [Us] Rated Supply Voltage: 12...48 V DC +/- 20 %
  • Communication Port Protocol: IEC 60870-5-104
  • Power Consumption In Va: 2 VA
  • Software Function: assistance in commissioning and operating the installation || security/authority verification || alarm || event log || Operating/Status report || reports and diagrams
  • Control Type: status illuminated push-button
  • Data Recording: sag and swell logs || harmonics logs || min/max of instantaneous values || demand values || event logs || sequence of event recording || counter || current value before fault
  • Breaking Capacity: 2000 VA
  • Analogue Input Type: 4 current 0.01...35 A 0.001 Ohm)
  • Type Of Measurement: current class 0.5 || voltage class 0.5 || energy class 1 IEC 61557-12
  • Synchronisation Time Between Inputs: 1 ms
  • Power Quality Analysis: voltage unbalance || individual harmonics || voltage sag and swell detection || harmonic distortion || voltage magnitude

Offer Sustainability

  • Rohs Exemption Information: Yes
  • Mercury Free: Yes
  • Environmental Disclosure: ENVPEP1605007
  • Sustainable Offer Status: Green Premium product
  • Reach Regulation: Reference contains Substances of Very High Concern above the threshold
  • California Proposition 65: WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Weee: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
  • China Rohs Regulation: X
  • Circularity Profile: ENVEOLI1605007
  • Eu Rohs Directive: Compliant

Environment

  • Product Certifications: CE
  • Ik Degree Of Protection: IK07 IEC 62262
  • Ambient Air Temperature For Operation: -40-70 °C
  • Height: 140 mm
  • Standards: IEC 60255-27 || IEC 61557-12 || IEC 62586-1 || IEC 61000-4-30:class S || IEC 61850
  • Electromagnetic Compatibility: electrical fast transient/burst immunity test level 4criteria A IEC 61000-4-4 || conducted RF disturbances level 3criteria A IEC 61000-4-6 || conducted disturbance emission level 4criteria A IEC 61000-4-16 || 100 kHz damped oscillating wave level 3criteria A IEC 61000-4-12 || radiated radio-frequency electromagnetic field immunity test level 4criteria A IEC 61000-4-3 || immunity to voltage dipscriteria A IEC 61000-4-29 || electrostatic discharge level 4criteria B IEC 61000-4-2 || surge immunity test level 3criteria A IEC 61000-4-5 || magnetic field at power frequency level 5criteria B IEC 61000-4-8 || conducted and radiated emissionsclass A EN 55022
  • Net Weight: 0.515 kg
  • Fixing Mode: clip-in DIN rail)
  • Ambient Air Temperature For Storage: -40-85 °C
  • Relative Humidity: 5-95 % IEC 60068-2-30
  • Ip Degree Of Protection: body IP2X IEC 60529 || front IP4X IEC 60529
  • Type Of Installation: indoor || outdoor in cabinet
  • Mechanical Robustness: vibrations 10-2000 Hz 1 gn 10 cycles IEC 60068-2-6 || bumps 10 gn 16 ms 1000 bumps non energized IEC 60068-2-29 || shocks 10 gn 11 ms 3 pulses in operation IEC 60068-2-27
  • Width: 45 mm
  • Depth: 140 mm
  • Operating Altitude: 6561.68 ft (2000 m)