Product Description
- Range Of Product: Easergy T300
 - Device Short Name: PS50
 
Complementary
- Output Voltage: 12 V DC || 48 V DC
 - Number Of Outputs: battery fault (BAT) 1 digital (relay) || main presence 1 digital (relay)
 - Product Or Component Type: power supply
 - Autonomy: 16 h
 - Charging Time: 24 h
 - Communication Port Support: RS485/RS232
 - Rated Short-Duration Power Frequency Withstand Voltage: 10 kV 50 Hz 1 min
 - [Us] Rated Supply Voltage: 110...220 V DC || 90...264 V AC 50/60 Hz
 - Communication Port Protocol: Modbus
 - Input Voltage Limits: 440 V AC/DC L-N)
 - Surge Withstand: 20 kV 1.2/50 µs
 - Protection Type: against short-circuits || integrated thermal protection
 - Battery Capacity: 24 Ah 12 V, Lead-Acid battery || 38 Ah 12 V, Lead-Acid battery
 - Product Compatibility: BAT24AH || BAT38AH
 
Offer Sustainability
- Rohs Exemption Information: Yes
 - Mercury Free: Yes
 - Environmental Disclosure: ENVPEP1605007
 - Sustainable Offer Status: Green Premium product
 - Toxic Heavy Metal Free: Yes
 - Reach Regulation: Free of Substances of Very High Concern above the threshold
 - California Proposition 65: WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
 - Reach Free Of Svhc: Yes
 - Weee: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
 - China Rohs Regulation: X
 - Circularity Profile: ENVEOLI1605007
 - Eu Rohs Directive: Compliant
 
Environment
- Product Certifications: CE
 - Ik Degree Of Protection: IK07 IEC 62262
 - Height: 190 mm
 - Standards: IEC 60255-27
 - Mounting Support: DIN rail
 - Electromagnetic Compatibility: electrical fast transient/burst immunity test level 4criteria A IEC 61000-4-4 || conducted and radiated emissionsclass A EN 55022 || conducted RF disturbances level 3criteria A IEC 61000-4-6 || conducted disturbance emission level 4criteria A IEC 61000-4-16 || 100 kHz damped oscillating wave level 3criteria A IEC 61000-4-12 || radiated radio-frequency electromagnetic field immunity test level 4criteria A IEC 61000-4-3 || immunity to voltage dipscriteria A IEC 61000-4-29 || electrostatic discharge level 4criteria B IEC 61000-4-2 || surge immunity test level 3criteria A IEC 61000-4-5 || magnetic field at power frequency level 5criteria B IEC 61000-4-8
 - Ambient Air Temperature For Operation: -40-70 °C
 - Net Weight: 2.75 kg
 - Ip Degree Of Protection: IP20 conforming to IEC 60529
 - Ambient Air Temperature For Storage: -40-70 °C
 - Relative Humidity: 5-95 % IEC 60068-2-30
 - Mechanical Robustness: vibrations 10-2000 Hz 1 gn 10 cycles IEC 60068-2-6 || bumps 10 gn 16 ms 1000 bumps non energized IEC 60068-2-29 || shocks 10 gn 11 ms 3 pulses in operation IEC 60068-2-27
 - Operating Position: vertical
 - Width: 270 mm
 - Overvoltage Category: IV
 - Depth: 71 mm
 - Operating Altitude: 6561.68 ft (2000 m)
 
              
Spec Sheet
Digest Catalog 05: Protection, Control, and Energy Automation (SEP 2022) - 0100CT1901_SEC-05_SEP22-2022 (pdf)
PowerLogic HU250 Installation guide - NHA77925-10_PowerLogic_HU250_Installation_Guide (pdf)
Easergy Builder - User Manual - SE-S856-MSS_Easergy+Builder+-+User+Manual_EN_4.0 (pdf)
Easergy T300 Quick start - NT00383-EN-07+-+Quick+start+T300 (pdf)
T300 Database User manual - NT00391-+08+-+T300+Database (pdf)
PowerLogic T300 User manual - NT00378-11-EN+PowerLogic+T300+User+Manual (pdf)
PS50 Installation guide - Easergy T300 - NT00375-05+-+PS50+installation+guide (pdf)
Easergy Builder software - Easergy+Builder_1.7.24.0_Release_Notes (pdf)
PowerLogic T300 Firmware - PowerLogic+T300+Release+2.8.2.zip
ESXP Certificate - IEC 62443-3-3 Large & Critical Architecture - ESXP+Certificate+-+IEC+62443-3-3+Large+%26+Critical+Architecture (pdf)
          Catalog
PowerLogic Easergy T300 Catalog - NRJED314621EN_(Web) (pdf)Digest Catalog 05: Protection, Control, and Energy Automation (SEP 2022) - 0100CT1901_SEC-05_SEP22-2022 (pdf)
User guide
PowerLogic HU250 without wireless - PKR45928-00_PowerLogic_HU250_without_Wireless_Installation_Guide (pdf)PowerLogic HU250 Installation guide - NHA77925-10_PowerLogic_HU250_Installation_Guide (pdf)
Easergy Builder - User Manual - SE-S856-MSS_Easergy+Builder+-+User+Manual_EN_4.0 (pdf)
Easergy T300 Quick start - NT00383-EN-07+-+Quick+start+T300 (pdf)
T300 Database User manual - NT00391-+08+-+T300+Database (pdf)
PowerLogic T300 User manual - NT00378-11-EN+PowerLogic+T300+User+Manual (pdf)
PS50 Installation guide - Easergy T300 - NT00375-05+-+PS50+installation+guide (pdf)
Software - Release
Easergy Builder software - Easergy+Builder+1.7.24.0.zipEasergy Builder software - Easergy+Builder_1.7.24.0_Release_Notes (pdf)
PowerLogic T300 Firmware - PowerLogic+T300+Release+2.8.2.zip
Certificate
PowerLogic T300 SL1 certification - PowerLogic+T300++SL1+certification++968_FSP_2462_00_23_en_el (pdf)ESXP Certificate - IEC 62443-3-3 Large & Critical Architecture - ESXP+Certificate+-+IEC+62443-3-3+Large+%26+Critical+Architecture (pdf)
Log in