Easergy SC150 CT-CAPA: Switch controller - 1/5 A - VPIS/VDS/PPACS sensors

Easergy SC150 CT-CAPA: Switch controller - 1/5 A - VPIS/VDS/PPACS sensors

Part Number: EMS59202

UPC:

View full details

Product Description

  • Range Of Product: Easergy T300
  • Device Short Name: SC150

Complementary

  • Communication Port Support: 2 ETHERNET RJ45
  • Measurement Voltage: VPIS single or three phases)0-30 V AC 50/60 Hz || VDS LRM single or three phases)0-30 V AC 50/60 Hz || PPACS single or three phases)0-30 V AC 50/60 Hz
  • Number Of Outputs: switch 2 digital (relay)
  • Continuous Output Current: 8 A
  • Memory Capacity: 4 MB
  • Output Voltage: motor 12...127 V DC || motor 90...220 V AC
  • Protection Type: ANSI 50/51 : overcurrent || ANSI 50N/51N : earth fault || ANSI 67 : directional phase overcurrent || ANSI 67N : directional earth fault || ANSI 47 : negative sequence overvoltage || ANSI 27 : undervoltage || ANSI 59 : overvoltage || ANSI 59N : neutral voltage displacement || ANSI 37 : phase undercurrent
  • Type Of Measurement: voltage || frequency || current
  • Product Or Component Type: MV switch controller
  • Irms Rated Making Capacity: 15 A 4 s
  • Measurement Current: 1-1 A || 5-5 A
  • Maximum Switching Voltage: 440 V AC
  • Number Of Inputs: 8 digital IEC 61131-2 type 3
  • [Us] Rated Supply Voltage: 12...48 V DC +/- 20 %
  • Communication Port Protocol: IEC 60870-5-104
  • Power Consumption In Va: 2 VA
  • Software Function: alarm || event log || assistance in commissioning and operating the installation || security/authority verification || reports and diagrams || Operating/Status report
  • Control Type: status illuminated push-button
  • Data Recording: counter || current value before fault || sequence of event recording || event logs || demand values
  • Breaking Capacity: 2000 VA
  • Analogue Input Type: 4 current 0.01...35 A 0.001 Ohm)
  • Type Of Measurement: current class 0.5 || voltage class 0.5
  • Synchronisation Time Between Inputs: 1 ms

Offer Sustainability

  • Rohs Exemption Information: Yes
  • Mercury Free: Yes
  • Environmental Disclosure: ENVPEP1605007
  • Sustainable Offer Status: Green Premium product
  • Reach Regulation: Reference contains Substances of Very High Concern above the threshold
  • California Proposition 65: WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Weee: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
  • China Rohs Regulation: X
  • Circularity Profile: ENVEOLI1605007
  • Eu Rohs Directive: Compliant

Environment

  • Product Certifications: CE
  • Ik Degree Of Protection: IK07 IEC 62262
  • Ambient Air Temperature For Operation: -40-70 °C
  • Height: 140 mm
  • Standards: IEC 60255-27 || IEC 61557-12 || IEC 62586-1 || IEC 61000-4-30:class S || IEC 61850
  • Electromagnetic Compatibility: electrical fast transient/burst immunity test level 4criteria A IEC 61000-4-4 || conducted RF disturbances level 3criteria A IEC 61000-4-6 || conducted disturbance emission level 4criteria A IEC 61000-4-16 || 100 kHz damped oscillating wave level 3criteria A IEC 61000-4-12 || radiated radio-frequency electromagnetic field immunity test level 4criteria A IEC 61000-4-3 || immunity to voltage dipscriteria A IEC 61000-4-29 || electrostatic discharge level 4criteria B IEC 61000-4-2 || surge immunity test level 3criteria A IEC 61000-4-5 || magnetic field at power frequency level 5criteria B IEC 61000-4-8 || conducted and radiated emissionsclass A EN 55022
  • Net Weight: 0.515 kg
  • Fixing Mode: clip-in DIN rail)
  • Ambient Air Temperature For Storage: -40-85 °C
  • Relative Humidity: 5-95 % IEC 60068-2-30
  • Ip Degree Of Protection: body IP2X IEC 60529 || front IP4X IEC 60529
  • Type Of Installation: indoor || outdoor in cabinet
  • Mechanical Robustness: vibrations 10-2000 Hz 1 gn 10 cycles IEC 60068-2-6 || bumps 10 gn 16 ms 1000 bumps non energized IEC 60068-2-29 || shocks 10 gn 11 ms 3 pulses in operation IEC 60068-2-27
  • Width: 45 mm
  • Depth: 140 mm
  • Operating Altitude: 6561.68 ft (2000 m)
Spec Sheet

Catalog

Digest Catalog 05: Protection, Control, and Energy Automation (SEP 2022) - 0100CT1901_SEC-05_SEP22-2022 (pdf)
PowerLogic Easergy T300 Catalog - NRJED314621EN_(Web) (pdf)

User guide

PowerLogic HU250 without wireless - PKR45928-00_PowerLogic_HU250_without_Wireless_Installation_Guide (pdf)
PowerLogic T300 User manual - NT00378-11-EN+PowerLogic+T300+User+Manual (pdf)
Easergy T300 Quick start - NT00383-EN-07+-+Quick+start+T300 (pdf)
Easergy Builder - User Manual - SE-S856-MSS_Easergy+Builder+-+User+Manual_EN_4.0 (pdf)
T300 Database User manual - NT00391-+08+-+T300+Database (pdf)
PowerLogic SC150 Installation guide - NHA91857-08_PowerLogic_SC150_Installation_Guide (pdf)
PowerLogic HU250 Installation guide - NHA77925-10_PowerLogic_HU250_Installation_Guide (pdf)

Software - Release

Easergy Builder software - Easergy+Builder_1.7.24.0_Release_Notes (pdf)
PowerLogic T300 Firmware - PowerLogic+T300+Release+2.8.2.zip
Easergy Builder software - Easergy+Builder+1.7.24.0.zip

Certificate

ESXP Certificate - IEC 62443-3-3 Large & Critical Architecture - ESXP+Certificate+-+IEC+62443-3-3+Large+%26+Critical+Architecture (pdf)
PowerLogic T300 SL1 certification - PowerLogic+T300++SL1+certification++968_FSP_2462_00_23_en_el (pdf)

Declaration of conformity

EU DECLARATION OF CONFORMITY T300 - EU+DECLARATION+OF+CONFORMITY+T300 (pdf)

Circularity Profile

Easergy T300, Circularity Profile, End of Life Instructions - ENVEOLI1605007_V2 (pdf)

Environmental Disclosure

Easergy T300, Environmental Disclosure, Product Environmental Profile - ENVPEP1605007_V1+-+T300+PEP (pdf)