Product Description
- Product Or Component Type: circuit breaker
- Product Name: PowerPact H
- Range: PowerPact
- Device Application: distribution
Contractual warranty
- Warranty: 18 months
Complementary
- Mounting Mode: unit mount lug)
- Network Frequency: 50/60 Hz
- Terminal Identifier: AL150HD
- [Ics] Rated Service Breaking Capacity: 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Trip Unit Technology: thermal-magnetic
- Height: 163 mm
- [Ue] Rated Operational Voltage: 690 V AC 50/60 Hz IEC 60947-3
- Tightening Torque: 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Mounting Support: lug
- Breaking Capacity Code: L
- Magnetic Tripping Current: 1450-1450 A
- Local Signalling: switched off (OFF) 1 trip indicator green)
- Number Of Slots: 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Protected Poles Description: 3t
- Electrical Connection: terminal nut line || lugs load
- Net Weight: 2.2 kg
- [Uimp] Rated Impulse Withstand Voltage: 8 kV IEC 60947-2
- Magnetic Hold Current: 800 A
- Control Type: toggle
- Circuit Breaker Application: HACR rated
- Wire Stripping Length: 16 mm
- Utilisation Category: category A
- Line Rated Current: 70-70 A
- Continuous Current Rating: 80 %
- Breaking Capacity: 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- [Ui] Rated Insulation Voltage: 750 V IEC 60947-2
- Suitability For Isolation: yes IEC 60947-2
- Communication Interface: Modbus || Ethernet
- Poles Description: 3P
- Quantity Per Set: 1
- Awg Gauge: AWG 14...AWG 3/0 aluminium/copper terminal
- Color: Black
- Width: 104 mm
- Depth: 86 mm
- Phase Connection: ABC
Offer Sustainability
- Rohs Exemption Information: Yes
- Mercury Free: Yes
- Environmental Disclosure: ENVPEP1311006EN
- Sustainable Offer Status: Green Premium product
- Pvc Free: Yes
- Reach Regulation: Reference contains Substances of Very High Concern above the threshold
- California Proposition 65: WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation: Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile: ENVEOLI1311006EN
- Eu Rohs Directive: Compliant
Environment
- Ambient Air Temperature For Operation: -2-70 °C
- Standards: UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications: UL || CSA || NOM
- Ip Degree Of Protection: front cover IP40 IEC 60529
- Pollution Degree: 3 IEC 60947-1
- Ambient Air Temperature For Storage: -50-85 °C
- Quality Labels: CE
- Operating Altitude: < 6561.68 ft (2000 m) without derating || 5000 m with derating
Spec Sheet
Digest Catalog 07: Miniature and Molded Case Circuit Breakers (MAR 2023) - 0100CT1901_SEC-07 (pdf)
PowerPact H- and J-Frame, Certificate, CSA - CoFC_H-J_MCCB_7-23-15 (pdf)
PowerPact H- and J-Frame, Certificate, CSA - CSA+H+and+J+MCP (pdf)
Recognition for BV Mode II Scheme - BV+for+H+J+and+L+manual+motor+controllers (pdf)
PowerPact H- and J-Frame, Certificate, CSA - CSA+H+and+J+Switches (pdf)
Technical drawing for H-Frame 15A - 150A 3-Pole Toggle Lug-Lug - H150-3P-LUG (pdf)
Technical drawing for H-Frame 15A - 150A 3-Pole Toggle Lug-Lug - H150-3P-LUG (dwg)
Technical drawing for H-Frame 15A - 150A 3-Pole Toggle Lug-Lug - H150-3P-LUG (dxf)
Terminal Cover and Lug Shield Kits for PowerPacT H- or J-Frame and TeSys GV5 Circuit Breakers - 48940-223-02 (pdf)
Catalog
PowerPacT H-, J-, and L-Frame Circuit Breakers Catalog - 0611CT1001 (pdf)Digest Catalog 07: Miniature and Molded Case Circuit Breakers (MAR 2023) - 0100CT1901_SEC-07 (pdf)
Brochure
Low Voltage Circuit Breakers for OEM Applications Brochure - 0106BR9806 (pdf)Certificate
PowerPact H- and J-Frame, Certificate, CSA - CSA+H+and+J+Breakers (pdf)PowerPact H- and J-Frame, Certificate, CSA - CoFC_H-J_MCCB_7-23-15 (pdf)
PowerPact H- and J-Frame, Certificate, CSA - CSA+H+and+J+MCP (pdf)
Recognition for BV Mode II Scheme - BV+for+H+J+and+L+manual+motor+controllers (pdf)
PowerPact H- and J-Frame, Certificate, CSA - CSA+H+and+J+Switches (pdf)
Technical Drawing
Trip Curve: PowerPacT H-Frame HD/HG/HJ/HL, 70A 80A 90A 100A Circuit Breaker, 50-3 - 50-03 (pdf)Technical drawing for H-Frame 15A - 150A 3-Pole Toggle Lug-Lug - H150-3P-LUG (pdf)
Technical drawing for H-Frame 15A - 150A 3-Pole Toggle Lug-Lug - H150-3P-LUG (dwg)
Technical drawing for H-Frame 15A - 150A 3-Pole Toggle Lug-Lug - H150-3P-LUG (dxf)
Instruction sheet
Removable Padlock Attachment S29370 - Installation Instructions - 48940-232-01 (pdf)Terminal Cover and Lug Shield Kits for PowerPacT H- or J-Frame and TeSys GV5 Circuit Breakers - 48940-223-02 (pdf)