Product Description
- The ODS0D uses passive infrared (PIR) technology to monitor a room for occupancy through a segmented Fresnel lens. This specialized lens divides the field-of-view into sensor zones. When a person passes into or out of a sensor zone, the sensor detects motion and switches two separate lighting loads ON. The lights will remain ON as long as there is an occupant moving through the sensor zones. Do you have a question about an occupancy sensor or vacancy sensor? Contact us to learn more.
- Provides automatic switching for two separate banks of fluorescent, incandescent, or low-voltage lighting from a single unit.
- Convenient dual pushbuttons provide manual-ON/OFF light switching of each load at any time.
- ODSOD-ID Conference Room Mode—primary and secondary relays switch lighting to last ON/OFF status when personnel enter room, providing a consistent lighting level from one occupancy period to the next. Both relays respond to Ambient Light Override, preventing lights from turning ON automatically during periods of ample natural light, for increased energy savings.
- ODS0D-ID Classroom Mode—both primary and secondary relays always switch lighting ON when personnel enter room, regardless of their ON/OFF status during last period of occupancy. Secondary relay only responds to Ambient Light Override—primary does not, ensuring that students and personnel never enter a darkened room.
- Presentation Mode feature for slide or film presentations allows push buttons to turn lights OFF and keep them OFF while the room is occupied.
- Auto adapting delayed-OFF time interval compensates for real-time occupancy patterns, preventing unnecessary ON/OFF switching.
- Exclusive Walk-Through feature provides increased energy savings by not leaving the lights ON for an extended period after only momentary occupancy.
- Non-Adaptive Mode disables Self-Adjusting Delayed-OFF Time and Walk-Through feature in applications where these features are not desired.
- Daylight harvesting light sensor measures the ambient light in the room when it first detects motion. It leaves the lights OFF if there is enough light in the room or turns the lights connected to the first relay ON if there is not enough light in the room.
- Low-profile design eliminates obtrusive “scanning-device” look. Elegant Decora wallplates complement any interior for sleek aesthetics; uses Decora wallplates and coordinates with Leviton’s popular line of Decora wiring devices.
- 180° field-of-view provides approximately 2100 square feet of coverage, suitable for a variety of commercial areas.
- Segmented Fresnel lens provides optimum sensitivity and performance. Designed with an extensive “minor motion” area where even slight body movements will be detected.
- Horizontal field-of-view may be adjusted between 180° and 60° arc by using integral blinders located on either side of the lens. No mask-ing tape required.
- Time delay adjustment for delayed-OFF time settings of 30 seconds, 5, 10, and 30 minutes. Allows customized adjustments to maximize energy savings.
- Vandal resistant PIR lens.
- False detection circuitry.
- Light Sensor adjustable Ambient Light Override ranges from approximately 2FC (20 LUX) to 500+FC (5000+ LUX).
- Manual-ON/auto-OFF mode for installations where manual-ON switching is required but auto-OFF switching is still desired for CEC Title T24 energy savings.
- To comply with CEC Title 24, red LED indicator light flashes when PIR sensor detects motion to verify detection is active.
- Beep warn - unit beeps 3 times after delayed-OFF time expires, then waits 10 seconds before turning lights OFF.
- One unit can be used for 120V through 277V lighting. Compatible with both electronic and magnetic ballasts.
- Primary relay switches at the zero crossing point of the AC power curve to ensure longer contact life and compatibility with electronic ballasts.
- Unit fits in standard single-gang wallbox and replaces two single-pole wall switches; ground connection required. Gangable with other devices.
- Exclusive Leviton H.I.S. Circuitry. Specifically designed to handle today’s high inrush electronic ballast loads and offer unmatched durability and service.
Color Variations
- Ivory
- Country of Origin: Mexico
Product Features
- Application: Classrooms, Multimedia Rooms, Daylight Harvesting, Conference Rooms, Day Care Centers, Offices, Lounges, Bi-Level or A/B Switching
- Color: Ivory
- Grade: Commercial
- Mounting: Wall Switch
- Product Line: ODS0D
- Sensor Technology: Passive Infrared (PIR)
- Sensor Type: Occupancy
- Technology: Passive Infrared
- Time Delay: 30s-30m
Performance Specifications
- Coverage (Sq.Ft.): 2100
- Pattern: 180°
Electrical Specifications
- Load Rating: Primary Relay Fluorescent: 1200VA @ 120V 2700VA @ 277V Incandescent: 800W @ 120V - Secondary Relay Fluorescent: 800VA @ 120V 1200VA @ 277V Incandescent: 800W @ 120V
- Neutral Wire Connection: Not Required
- Voltage: 120/230/277 VAC
- Frequency: 50/60Hz
- Power Consumption: 120V - 110mW, 277V - 270mW
- Wiring: Primary Relay No. 16 AWG leads: Line-Black, Load-Blue, Ground-Green - Secondary Relay N0. 18 AWG isolated contact leads: (2) Red
Mechanical Specifications
- Mounting Type: Wall Switch
- Size: Height 4.06" (103.2mm), Width 1.75" (44.4mm), Depth 1.83"(47mm), Install Depth 1.35"(34.4mm), Install Height 2.60"(66.2mm)
- Switch Type: Single-Pole, Dual Relay
- Relay Type: Dual Relay
Environmental Specifications
- Operating Temperature: 32° to 122°F (0° to 50°C)
- Relative Humidity: 20% to 90% non-condensing
- Storage Temperature Range: 14° to 185°F (-10° to 85°C)
Warranty
- Warranty: 5-Year Limited
Standards and Certifications
- Listings: cUL/US Certified, can be used to comply with Title 24, Part 6 occupancy sensing requirements, FCC Compliant
- USMCA Compliant: Yes
Type
- Product Type: Occupancy Sensor
Dual_Relay_Decora_Wall_Switch_PIR_Occupancy_Sensor_ODS0D-ID_Data_Sheet_Occupancy_Sensors.pdf
Application_Note_CHANGES_IN_TITLE_24.pdf
Application_Note_ENERGY_POLICY_ACT_OF_2005.PDF
Application_Note_IECC_VS_ASHRAE_90.1_2001.pdf
Application_Note_IRS_AND_ENERGY_MANAGEMENT.pdf
Application_Note_READY_TO_ACHIEVE_LEED_POINTS.pdf
Application_Note_ULTRASONIC_AND_MULTI_TECH_ADA_FDA.pdf
Tech_Article-PIR_and_US_Occupancy_Sensor_Technologies.pdf
Tech_Article-Microphonics_and_Occupancy_Sensors.pdf
Tech_Article-Occupancy_Sensing_and_Ballast_Life.pdf
ODS0D-TD_Instructions_FR.pdf
ODS0D-TD_Instructions_SP.pdf
Application Note
Occupancy_Sensor_Technology_Intro.pdfApplication_Note_CHANGES_IN_TITLE_24.pdf
Application_Note_ENERGY_POLICY_ACT_OF_2005.PDF
Application_Note_IECC_VS_ASHRAE_90.1_2001.pdf
Application_Note_IRS_AND_ENERGY_MANAGEMENT.pdf
Application_Note_READY_TO_ACHIEVE_LEED_POINTS.pdf
Application_Note_ULTRASONIC_AND_MULTI_TECH_ADA_FDA.pdf
Tech_Article-PIR_and_US_Occupancy_Sensor_Technologies.pdf
Tech_Article-Microphonics_and_Occupancy_Sensors.pdf
Tech_Article-Occupancy_Sensing_and_Ballast_Life.pdf
Instruction Sheet
ODS0D-TD_Instructions.pdfODS0D-TD_Instructions_FR.pdf
ODS0D-TD_Instructions_SP.pdf