Product Description
- Trip Unit Technology: electronic, basic, ET 1.0, LI
- Range Of Product: I-Line
- Circuit Breaker Type: M-frame
- Product Or Component Type: plug-in unit
Contractual warranty
- Warranty: 18 months
Complementary
- Line Rated Current: 350-350 A
- Height: 615 mm
- Mounting Mode: bolt-on
- Poles Description: 3P
- Protection Type: circuit breaker
- Condition Of Use: horizontal installation
- Wiring Configuration: 4-wire (integral ground bus)
- Width: 1275 mm
- Depth: 631 mm
- Phase: 3 phase
- [Ue] Rated Operational Voltage: 600 V AC
- Awg Gauge: AWG 3/0...500 kcmil 3 phase and neutral || AWG 6...300 kcmil 4 ground
- Breaking Capacity: 100 kA 240 V AC || 65 kA 480 V AC || 25 kA 600 V AC
- [Ics] Rated Service Short-Circuit Breaking Capacity: 80 %
Offer Sustainability
- China Rohs Regulation: Product out of China RoHS scope. Substance declaration for your information.
- Rohs Exemption Information: Yes
- Mercury Free: Yes
- Environmental Disclosure: ENVPEP1410002EN
- Sustainable Offer Status: Green Premium product
- Eu Rohs Directive: Compliant
- Reach Regulation: Reference contains Substances of Very High Concern above the threshold
- California Proposition 65: WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Environment
- Product Certifications: CSA C22.2 No 27 || UL listed file E22182
- Standards: UL 857
Spec Sheet
Trip Curve: MicroLogic 2.0, 3.0, 5.0, and 6.0 Std, A, P, and H Trip Unit - Instantaneous Override Values - 613-10 (pdf)
Certificate
I-Line® Busway, Certificate, UL - E22182-6-31-20120202-Certificate_of_Compliance (pdf)Instruction sheet
I-Line™ Plug-In Units: PTMx/PTPx (250–1200 A Circuit Breakers) - 45225-094-01 (pdf)Environmental Disclosure
PEP_I-Line I & II Busway Circuit Breaker Plug-in Unit - ENVPEP1410002EN (pdf)Technical Drawing
Trip Curve: ET 1.0 Electronic Trip Unit - Long-time Pickup and Delay Instantaneous Pickup and Delay 2x-10x - 613-14 (pdf)Trip Curve: MicroLogic 2.0, 3.0, 5.0, and 6.0 Std, A, P, and H Trip Unit - Instantaneous Override Values - 613-10 (pdf)